How must the conductors of one circuit, including the grounded and equipment grounding conductors, be routed?

  1. In separate raceways for each of the phases
  2. With the neutral run in its own raceway
  3. By any route that ends at the same box
  4. Together in the same raceway, cable or trench
Show the answer

D. Together in the same raceway, cable or trench

All conductors of a circuit are kept together in the same raceway, cable, trench or cord. Keeping them together cancels magnetic fields and keeps the fault path impedance low.

Reference: NEC 2023, 300.3(B)

A hole is bored through a wood stud for NM cable. If no steel plate is used, the edge of the hole must be at least how far from the nearest edge of the stud?

  1. 3/4 in.
  2. 1 in.
  3. 1-1/4 in.
  4. 1-1/2 in.
Show the answer

C. 1-1/4 in.

The hole edge must be at least 1-1/4 in. from the nearest edge of the framing member, or a steel plate must protect the cable. That depth keeps normal drywall screws and nails from reaching the cable.

Reference: NEC 2023, 300.4(A)(1)

What is the minimum cover for Type UF cable buried directly in a yard, with no reduction for GFCI protection or other conditions?

  1. 6 in.
  2. 12 in.
  3. 18 in.
  4. 24 in.
Show the answer

D. 24 in.

Direct-buried cables need 24 in. of cover in the general case. The 18 in. depth is for nonmetallic raceways such as PVC, and 6 in. is for rigid or intermediate metal conduit.

Reference: NEC 2023, 300.5(A)