Low Voltage & Structured Cabling Practice Test

Copper and fibre cabling, terminations, pathways, grounding, power-limited circuits, security and access systems, testing and safety for limited energy licences and cabling certifications.

185 questions · 6 topics · free, no sign-up

Mixed practice test

10 questions, graded as you go, with the reason for every answer. No sign-up.

Timed mock exam

50 questions in 60 minutes, drawn from every topic. No answers shown until the end, then a score, your weakest topics and a review of what you missed.

Practise by topic

Sample questions

Which pair lands on pins 4 and 5 in both the T568A and the T568B wiring schemes?

  1. The blue pair
  2. The orange pair
  3. The green pair
  4. The brown pair
Show the answer

A. The blue pair

The blue pair (pair 1) sits on the centre pins 4 and 5 in both schemes, and the brown pair is on 7 and 8 in both. Only the orange and green pairs change places between T568A and T568B.

Reference: ANSI/TIA-568 series, pin and pair assignments (T568A and T568B)

What jacket colour identifies indoor OM3 or OM4 laser-optimised multimode cable?

  1. Orange
  2. Aqua
  3. Yellow
  4. Lime green
Show the answer

B. Aqua

OM3 and OM4 are jacketed aqua. Orange is used for the older OM1 and OM2 multimode, yellow for single-mode and lime green for OM5 wideband multimode.

Reference: ANSI/TIA-598, fibre colour coding

Under the telecommunications pathway standard, what is the most bending allowed in a conduit run between pull points?

  1. One 90-degree bend (90 degrees total)
  2. Three 90-degree bends (270 degrees total)
  3. Four 90-degree bends (360 degrees total)
  4. Two 90-degree bends (180 degrees total)
Show the answer

D. Two 90-degree bends (180 degrees total)

Telecommunications conduit is limited to the equivalent of two 90-degree bends between pull boxes so that cable can be pulled without exceeding its tension limit. Four quarter bends (360 degrees) is the general limit in the electrical code for power raceways, and it is too many for data cable.

Reference: ANSI/TIA-569, conduit pathways

Which NEC article covers the wiring of fire alarm systems, including power-limited fire alarm circuits?

  1. Article 725
  2. Article 640
  3. Article 760
  4. Article 820
Show the answer

C. Article 760

Fire alarm circuits have their own article, 760, with their own cable types such as FPL, FPLR and FPLP. Article 725 covers Class 2 and Class 3 circuits, which is where many people look first.

Reference: NEC 2023, Article 760

Why is a dual-technology (PIR plus microwave) motion detector less prone to false alarms than a PIR alone?

  1. Either technology can trip the alarm independently
  2. Both technologies must detect at the same time to trip
  3. The microwave section doubles the coverage range
  4. The PIR section is switched off while the heater runs
Show the answer

B. Both technologies must detect at the same time to trip

The two sensors react to different things, so requiring both to agree rejects causes that fool only one of them, such as a heating vent (PIR) or movement behind a thin wall (microwave). If either one alone could trip the alarm, false alarms would increase.

Reference: Intrusion detection principles; sensor manufacturer data